Table of Contents

Configure digital inputs

The Sound Card can start and stop sound playback from TTL signals on its digital inputs (IN0, IN1), with a volume set per input. The inputs can also be used as general-purpose digital inputs (e.g. to timestamp events from external devices on the device clock). Refer to the connections article to set up a digital input signal on IN0, which we will use for the rest of these examples.

Note

Pure tone playback from the internal sine wave generator is currently limited (as of firmware v3.0) to the Right Channel. Connect the amplifier and speaker to this channel if you plan to play pure tones.

This article covers how to configure the digital input mode, set the volume of triggered sounds, and visualize the state of the inputs in Bonsai.

The complete workflow is shown below. Copy and paste it into Bonsai to get started immediately, or build each section by following the step-by-step instructions in the following sections.

Configure digital inputs

Note

IN2 has no events or trigger modes yet. Its level can only be read through the InputState register.

Set mode and sound

Each digital input line has a configuration mode register that sets what the signal does (e.g. ConfigureDI0 for IN0) as well as a start sound register that sets the sound index or frequency to play (e.g. StartOnDI0 for IN0).

ConfigureDI0 has four options:

Mode Description
Digital The input is read as a general-purpose digital input and reports its state as InputState events.
Start A rising edge starts the sound. A stored sound plays to the end unless it is stopped early and a pure tone keeps playing. Use a Stop command or another digital input in Stop mode to end playback.
StartAndStop A rising edge starts the sound and a falling edge stops it.
Stop A rising edge stops the sound that is playing.

StartOnDI0 follows the same rules as Start, whereby values from 2 to 31 select a stored sound index, and values from 32 to 40000 set the frequency of a pure tone in Hz.

There are multiple ways to combine and use the digital input functionality. This example will demonstrate how to configure the digital input to start and stop pure tone playback.

Set mode and sound

  • Insert a KeyDown operator and set the Filter property to A.
  • Insert a CreateMessage operator and configure the following properties:
    • Payload - Select ConfigureDI0Payload.
    • ConfigureDI0 - Select StartAndStop.
  • Insert a MulticastSubject operator named SoundCard Commands.
  • Insert a CreateMessage operator and configure the following properties:
    • Payload - Select StartOnDI0Payload.
    • StartOnDI0 - Set the frequency in Hz to start (e.g. 500).
  • Insert a MulticastSubject operator named SoundCard Commands.

Run the workflow and press A to set the configuration, then send a TTL signal from the external device to IN0. The 500 Hz tone plays while the signal is high and stops when it goes low.

Note

Just like sounds triggered from Bonsai, sounds triggered from the digital inputs report Start and Stop events. Refer to the Play sounds article to visualize the events.

Set volume of triggered sounds

The volume for sounds played through the digital input triggers is set separately from the attenuation registers covered in the Adjust volume article. Each digital input line has its own attenuation registers for the left and right channel (e.g. AttenuationLeftDI0 and AttenuationRightDI0 for IN0).

Set volume of triggered sounds

  • Insert a KeyDown operator and set the Filter property to S.
  • Insert a CreateMessage operator and configure the following properties:
    • Payload - Select AttenuationLeftDI0Payload.
    • AttenuationLeftDI0 - Set the attenuation of the left channel (e.g. 200 = -20 dB). The default value is 60 (-6 dB).
  • Insert a MulticastSubject operator named SoundCard Commands.
  • Insert a CreateMessage operator and configure the following properties:
    • Payload - Select AttenuationRightDI0Payload.
    • AttenuationRightDI0 - Set the attenuation of the right channel (e.g. 200 = -20 dB). The default value is 60 (-6 dB).
  • Insert a MulticastSubject operator named SoundCard Commands.

Run the workflow, press S, and trigger IN0 again. The sound plays at the new volume.

Warning

A sound triggered from a digital input also overwrites the attenuation set with the registers covered in the Adjust volume article. For example, if AttenuationLeft is set to 200 (-20 dB), and AttenuationLeftDI0 is set to 100 (-10 dB), the triggered sound plays at -10 dB, and sounds played afterward with Start also play at -10 dB.

Visualize digital input events

The digital inputs do not report a line status under any of the trigger mode configurations (Start, StartAndStop, Stop). To use them as general purpose digital inputs, set the mode to Digital. Rising and falling edges are reported as InputState events. This example reconfigures IN0 to Digital mode, and demonstrates how to visualize incoming events.

Visualize digital input events

  • Insert a KeyDown operator and set the Filter property to D.
  • Insert a CreateMessage operator and configure the following properties:
    • Payload - Select ConfigureDI0Payload.
    • ConfigureDI0 - Select Digital.
  • Insert a MulticastSubject operator named SoundCard Commands.

In a separate branch:

Run the workflow, press D, and send a TTL signal to IN0. The visualizer will display:

DI0@15346.973344
None@15347.102112

The first value lists the inputs that read high, in this case DI0 on the rising edge and None on the falling edge, and the second number is the timestamp on the device clock.